PT65H High Capacity Float & Thermostatic Steam Trap

By Pennant Engineering Pvt. Ltd.

High-capacity cast iron float & thermostatic steam trap with internal air vent for large condensate loads, in double-orifice and rotary-orifice variants, rated to 250 psig and 425°F.

Specifications

Sizes
NPS 1½", 2"
Available types
PT65H (thermostatic air vent), PT65H S (SLR), PT65H C (air vent + SLR)
Orifice variants
Double orifice (65 psi range), rotary orifice (200 psi range)
Operation
Modulating discharge at steam temperature with thermostatic air vent
Use
Saturated and superheated steam
Max allowable pressure (PMA)
250 psig
Max allowable temperature (TMA)
425°F
Max operating pressure (PMO)
200 psig
Body / shell design rating
286 psig @ 800°F
Cold hydro test pressure
375 psig
Max differential pressure
Double orifice: 65 psi / Rotary orifice: 200 psi
End connection
Screwed (NPT/BSPT/BSP)
Weight (screwed)
64 lbs
Installation
Horizontal, flow left to right, below equipment drain point with float arm horizontal
Body material
Cast Iron
Internals
Stainless Steel (AISI 304)
Valve seat
AISI 410/420
Available spares
Housing assembly, air vent assembly, gaskets

Overview

The PT65H is a high-capacity float and thermostatic steam trap with an internal thermostatic air vent, in cast iron construction with stainless steel internals, sized 1½" and 2". Designed for draining large condensate loads from low and medium pressure steam heating and process equipment such as unit heaters, heat exchangers, driers and jacketed vessels, it gives a modulating discharge at steam temperature with excellent automatic air venting. It is offered in double-orifice (high capacity at low differential) and rotary-orifice (wide 200 psi working range) variants, with steam lock release (SLR) options. Rated to 250 psig maximum allowable pressure and 425°F. Supplied, sized and serviced for steam systems across Nepal.

Features & Benefits

  • The two orifice options make this one body serve two very different duties: the double-orifice variant gives very high capacity at low differential pressure (nearly 7000 lbs/hr at 0.5 psi), while the rotary-orifice variant trades initial capacity for a much wider 200 psi working range, so the buyer picks by whether the system runs at low differential and high load or across a broad pressure range.
  • High capacity in a single 1½"/2" body means one PT65H can replace several smaller traps on a large heat exchanger or drier, reducing installation points and the associated leak and maintenance surface.
  • The internal thermostatic air vent clears the large air volume these big process units hold at start-up, getting equipment to temperature faster than a bucket trap that vents air slowly.
  • Discharging condensate at steam temperature keeps the full heating surface active and avoids condensate backing up and sub-cooling, which is the main efficiency argument for a float trap over a thermostatic-only trap on process equipment.
  • The rotary-orifice variant's ability to hold capacity across 200 psi suits systems where the differential swings widely with load, since a fixed double-orifice would either waste steam at low differential or starve at high differential.
  • Cast iron body keeps cost reasonable for this capacity class at the 250 psig ceiling; for higher pressure or SW/FL ends, the cast steel PT66 is the step up in the same high-capacity family.
  • SLR (steam lock release) option handles equipment where condensate gets locked behind trapped steam, such as siphon-drained rotating cylinders, which a plain float trap cannot clear on its own.

Trap Discharge Capacity

All dimensions in lbs/hr
Trap Discharge Capacity (lbs/hr) — Differential Pressure (psi)
ModelSize0.512510152030406590115145170185200
PT65H-65 (Double Orifice)1½", 2"693084701148013300140501628017650218602540033660------------------
PT65H-200 (Rotary Orifice)1½", 2"204027003820605085801025012100144901716021730251002900032400355003690038340
  • Discharge capacity in lbs/hr against differential pressure in psi.
  • Two orifice variants: double orifice (max 65 psi differential) and rotary orifice (max 200 psi differential).

Materials of Construction

All dimensions in
ComponentMaterialSpecification
BodyCast Iron---
CoverCast Iron---
GasketNon CAF---
Valve SeatAISI 410/420Double-orifice variant
Valve Seat HousingAISI 304Rotary-orifice variant
Valve PinAISI 410/420---
Ball Float / Float AssemblyAISI 304---
LeverAISI 304Double-orifice variant
StemAISI 304---
Air VentStainless Steel / AISI 304---
BoltHigh Tensile---
Drain PlugCarbon Steel---
SLR UnitAISI 304---
  • Materials span both the double-orifice and rotary-orifice variants; the specification column notes parts specific to one variant.